RNE Modular Controller Field Technical Guide

INSTALLATION AND WIRING

21

GND

TMP

Space Temperature Sensor

OVR

R

E

L

O

C

R

E

M

R

O

A

W

AUX

Wire Required For

Sensors With Slide

Adjust Option Only

Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply
Air Temperature Reset Signal Option (By
Others) May Be Connected To An AI7 On
The RNE Controller. Only One Option Is
Allowed, Not Both.

AI1

AI7

GND

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

RNE Controller

Set Jumper For THERM

When Space Sensor Slide

Adjust Is Wired To AI7

AI7 SET

Figure 11: Remote Supply Air Temperature Reset Signal Wiring

Space Temperature Sensor

The OE210, OE211, OE212, OE213 Space Temperature Sensor is typi-
cally used for constant volume HVAC unit applications controlling one
zone. The Space Temperature Sensor is a 10K Type III thermistor sensor
and should be mounted approximately 5 feet above the fl oor in the space
that is to be controlled. The Space Temperature Sensor is available as a
sensor only, sensor with override button, sensor with slide adjust, and
sensor with slide adjust and override confi gurations.

When the Remote Supply Air Temperature Reset Signal option is needed,
the Slide Offset option on the Room Sensor cannot be used. Only one
of these options may be used on the RNE Controller.

See Figure 10 below for complete Space Temperature Sensor wiring
details.

Remote Supply Air

Temperature Reset Signal

(By Others)

0-5 VDC or 0-10 VDC Signal

GND

Note:
Either The Slide Offset Option For The Space Temperature
Sensor Or The Remote Supply Air Temperature Reset
Signal Option (By Others) May Be Connected To AI7 On
The RNE Controller. Only One Option Is Allowed, Not Both.

AI7

GND

RNE Controller

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Regardless of Whether the Remote

SAT Reset Signal Has Been

Configured For 0-5 or 0-10 VDC,

Jumper Must Be Set For 0-10V

AI7 SET

Figure 10: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring

Remote SAT Reset Signal

Remote SAT Reset Signal

A Remote Supply Air Temperature Reset Signal can be connected to AI7
for applications requiring remote reset of the Supply Air Temperature
Setpoint.

When the Slide Offset option on the Room Sensor is used, the Remote
Supply Air Temperature Reset Signal cannot be used. Only one of these
options may be used on the RNE Controller.

The RNE Controller can accept either a 0-5 VDC signal or a 0-10 VDC
signal on this input.

See Figure 11 below for complete Remote SAT Reset Signal wiring
details.