INSTALLATION AND WIRING

29

Binary Inputs Wiring

Figure 20: OE356-01-BI – 4 Binary Input Expansion Module Wiring

Dirty Filter - N.O. Contact
Proof Of Flow - N.O. Contact
Remote Forced Occupied - N.O. Contact

Emergency Shutdown - N.C. Contact

BI3

BI4

COM

BI1

24 V

A

C

GND

BI2

Modular Cable

Connect To RNE

Controller

Modular Cable

Connect To Next Expansion

Board (When Used)

24 VAC

GND

4 Binary Input

Expansion Module

5 VA Minimum Power

Required For

4 Binary Input

Expansion Module

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity
will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the
expansion modules and the controller are always powered together. Loss of power to the expansion module will
cause the controller to become inoperative until power is restored to the expansion module.

BI1

BI2

BI3

BI4

COM

VCM BIN EXP

BOARD

YS102364 REV1

24V

AC

GND

PWR

4 Binary Inputs Located On 4 Binary

Input Expansion Module

If your HVAC unit only requires an Emergency Shutdown (Smoke
Detector/Firestat or other shutdown conditions), Dirty Filter, Proof of
Flow or Remote Forced Occupied Inputs or any combination of these 4
inputs and you don’t need any of the other inputs or outputs provided on
the OE333-23-EM VCM-X Expansion Module, you can use the OE356-
01-BI 4 Binary Input Expansion Module for these inputs.

The transformer used for powering the 4 Binary Input Expansion Module
must also be used to power the binary inputs. See Figure 20 below for
detailed wiring.

WARNING: Do not apply any voltage greater than 24 VAC
to the binary inputs. Higher voltages will damage the expansion
module and possibly other components on the system.