Installation and wiring, Sat & rat sensor wiring, Rne modular controller field technical guide 22 – Orion System RNE Modular Controller User Manual

Page 22: Supply air & return air temperature sensor, Zone

Advertising
background image

Zone

Zone

INSTALLATION AND WIRING

RNE Modular Controller Field Technical Guide

22

SAT & RAT Sensor Wiring

Figure 12: OE230 / OE231 – Supply Air and Return Air Temperature Sensor Wiring

Mount In HVAC

Unit Supply

Air Duct

Mount In HVAC

Unit Return

Air Duct

Supply Air Temperature Sensor

Return Air Temperature Sensor

Be Sure The Jumper Is Set For THERM

On AI2 & AI3 For Supply

& Return Air Temperature Sensors

When Used

Note: The Supply Air Temperature Sensor Always
Wires To The AI2 Input On The RNE Controller Unless
Using The MODGAS II And/Or MHGRV II Controllers
As Stand-Alone.

AI2

AI3

GND
GND

RNE Controller

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Supply Air & Return Air Temperature

Sensor

The OE231 Supply Air & Return Air Temperature Sensors must be
wired as shown in Figure 12 below for proper operation. The Supply
Air & Return Air Temperature Sensors are 10K Type III thermistor
sensors. The Supply Air Temperature Sensor should be mounted in the
unit discharge plenum or in the supply air duct. The Return Air Tem-
perature Sensor should be mounted in the return air duct. If the system
has a Zoning Bypass Damper installed, be sure the return air sensor is
located upstream of the bypass duct connection.

NOTE: If your AAON

®

HVAC unit is using the AAON

®

MODGAS-X Controller and/or the AAON

®

MHGRV-

X Controller, the Supply Air Temperature Sensor must
always be connected to the RNE Controller unless you
are using the AAON

®

MODGAS-X and/or AAON

®

MHGRV-X Controllers as stand-alone.

Advertising