Overview, Features and applications – Orion System RNE Modular Controller User Manual

Page 4

Advertising
background image

OVERVIEW

RNE Modular Controller Field Technical Guide

4

Features

The RNE Modular Controller (OE332-23E-RNE-A) is designed with 7
analog inputs, 2 analog outputs, and 5 relay outputs. Each RNE Control-
ler’s input and output capabilities can be expanded with the VCM-X
Expansion Module (OE333-23-EM), the 12 Relay Expansion Module
(OE358-23-12R), and the 4 Binary Input Expansion Module (OE356-
01-BI) by means of a modular cable.

The RNE Controller also allows various E-BUS modules to connect
directly to it. These would include the Full Digital Module, the Two
Condenser Head Pressure Module, and the Water Source Heat Pump
Modules.

Each RNE Controller can be confi gured for control of VAV Units (with
or without VAV/Zone Controllers), Constant Volume Units, and Make-
Up Air Units. Features include the following:

Up to a Combined Total of 20 Stages of Heating & Cooling

Modulating Cooling Outputs (VFD Compressor or Chilled

Water

Valve

Control)

Modulating Heating Output ( Hot Water Valve,

Steam Valve, SCR Electric Heat Control)

Full Integration with the AAON

®

MODGAS-X Modulating

Natural Gas Controller

Full Integration with the AAON

®

MHGRV-X Modulating

Hot Gas Reheat Controller

Confi gurable for Heat Pump Applications

Advanced Dehumidifi cation Capabilities

Air Flow Monitoring of Outdoor Air, Supply Air,

and Return Air Streams

Air Flow Control of Outdoor Air Damper

Single Zone VAV Control

Primary/Secondary Heating Control

Adaptive Supply Air Reset

Selectable Control Sensor

Fan Proving Interlock

Features and Applications

Dirty Filter Alarm

Emergency Shutdown Input (Smoke Detector/Firestat or

other Shutdown Conditions)

Drybulb/Wetbulb Control of Economizer Operation

Building Pressure Control

Remote Override Capabilities

IAQ Economizer Reset

Title 24 Economizer Certifi ed

7-Day, 2-Event-per-Day Scheduling

14 Holiday Event Scheduling

Optimal Start Scheduling

Trend Logging Capability

Static Pressure Control for Filter Loading Applications

Accepts Remote HVAC Mode Selection Via Contact

Closure On VCM-X Expansion Module

Confi gurable for AAON

®

PAC and DPAC Applications

Heat Wheel - On/Off Control

Confi gurable for R22 and R410-A refrigerant

Head Pressure Control

Full Digital Control

Water Source Heat Pump Monitoring

Most common HVAC unit control applications can be confi gured using
only the RNE Controller. If the application requires more inputs and/
or outputs, optional expansion modules are available to provide for ad-
ditional analog, binary, or digital inputs and outputs as required.

The available expansion module confi gurations allow for 4 or 8 addition-
al binary inputs, 4 additional analog inputs, 5 additional analog outputs,
and up to 16 additional binary (relay) outputs. The various expansion
modules plug into the RNE Controller by means of a modular cable.

Advertising