RNE Modular Controller Field Technical Guide

SEQUENCE OF OPERATION

67

Title 24 Economizer & VAV/Zone Controller Alarms

Title 24 Economizer Alarms

Economizer Temperature Sensor Failure

Outside Air or Supply Air Temperature Sensor is shorted or missing.

Economizer Not Economizing When it Should

Economizer is enabled but not following the desired Economizer posi-
tion commanded.

Economizer Is Economizing When It Should Not

Economizer is not enabled but the feedback signal indicates a position
more open than the minimum.

Economizer Damper Not Modulating

Economizer is enabled but not within 10% of desired position within
150 seconds.

Economizer Excess Outdoor Air Filter

Economizer feedback is lost or Economizer is not following commanded
position.

VAV/Zone Controller

Alarms

Space Sensor Failure Alarm

If the controller detects an open or short on the Space Sensor input, this
alarm will be generated.

CFM Sensor Failure Alarm

If the Air Flow Constant (K Factor) is set to any value other than zero,
and the controller does not detect the Airfl ow Sensor, this alarm will
be generated.

Damper Opening Alarm

After initial calibration, if the damper is called to be fully open and
cannot reach that position within approximately 2 minutes, this alarm
will be generated.

Damper Closing Alarm

After initial calibration, if the damper is called to be fully closed and
cannot reach that position within approximately 2 minutes, this alarm
will be generated.

High Space Temp Alarm

If the zone temperature is above the Cooling Setpoint by the Hi Zone
Alarm Offset (user adj.) for the Zone Alarm Delay Period (user adj.),
this alarm will be generated.

Low Space Temp Alarm

If the zone temperature is below the Heating Setpoint by the Lo Zone
Alarm Offset (user adj.) for the Zone Alarm Delay Period (user adj.),
this alarm will be generated.

Damper Feedback Failure Alarm

If the controller fails to detect the actuator feedback signal, this alarm
will be generated.