Installation and wiring, Economizer damper actuator wiring, Rne modular controller field technical guide 24 – Orion System RNE Modular Controller User Manual

Page 24: Economizer damper actuator, Zone

Advertising
background image

Zone

Zone

INSTALLATION AND WIRING

RNE Modular Controller Field Technical Guide

24

Figure 14: Economizer Damper Actuator Wiring

24 VAC Power Source

Sized For Actuator VA Load

24 V

A

C

GND

2-10 VDC

Output

RNE Controller

GND

AO1

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Economizer Damper Actuator

(Belimo Actuator Shown)

Y1 3

+ 2

COM - 1

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturer Wiring

Instructions

Economizer Feedback 5

NOTE: For Economizer

Actuator Feedback Signal,

See

Wiring For The

VCM-X Expansion Module.

AI3

Economizer Damper Actuator

The Economizer Damper Actuator signal voltage output is a 2-10 VDC
output. This signal output is used by the RNE Controller to modulate
the Economizer Damper Actuator in order to control the amount of
Outdoor Air delivered to the HVAC unit for Free Cooling and/or Indoor
Air Quality requirements. See Figure 14 for detailed wiring.

WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the actuator or RNE
Controller.

Economizer Damper Actuator Wiring

Advertising