INSTALLATION AND WIRING

25

Supply Fan VFD Signal or Zoning

Bypass Damper Actuator Signal

The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a
0-10 VDC output. This signal output can be connected to the Supply
Fan Variable Frequency Drive to modulate the Supply Fan speed and
control Duct Static Pressure utilizing the Duct Static Pressure Sensor
connected to the RNE Controller. Alternatively, it can be connected to a
Zoning Bypass Damper Actuator that will modulate the Zoning Bypass
Damper Actuator to control Duct Static Pressure utilizing the Duct Static
Pressure Sensor connected to the RNE Controller. A Duct Static Pressure
Sensor must be connected in order for the VFD or Zoning Bypass Damper
Actuator to operate. See Figures 15 and 16 below for detailed wiring.

Supply Fan VFD Signal and Zoning Bypass Damper Actuator

CAUTION: Variable Frequency Drive units can cause large
transient noise spikes which can cause interference to be propagated
on other electronic equipment. Use shielded wire wherever possible
and route all sensor and controller wiring away from the Variable
Frequency Drive and the HVAC Unit electrical wiring.

Figure 16: Zoning Bypass Damper Actuator Wiring

+

Supply Fan Variable Frequency Drive

(By Others)

_

0-10VDC Input From AO2

Shield

GND

Caution:

The VFD Unit Must Be Configured For 0-10 VDC Input.
The Input Resistance At The VFD Must Not Be Less
Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.

Note:

Wire To The VFD Using 18 GA Minimum 2
Conducter Twisted Pair With Shield Cable.
Wire Shield To GND As Shown

AO2

GND

Shield

RNE Controller

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Bypass Damper Actuator

(Belimo Actuator Shown)

0-10 VDC

24 VAC Power Source

Sized For Actuator VA Load

GND

24 VAC

3 (Y)

5 (U)

2 (+)

1 (-)

Belimo Actuator Wiring Shown.

Consult Factory For Other

Manufacturer Wiring Instructions.

RNE Controller

GND

AO2

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Figure 15: Supply Fan VFD Wiring