RNE Modular Controller Field Technical Guide

INSTALLATION AND WIRING

41

Connect To

RNE Controller

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

HSSC Cable

Connect To Two Condenser Head

Pressure II Module

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHP-X2

Water Source

Heat Pump X2 Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. 2 ENABLE

COMP. 1 ENABLE

R1

R5

R3

COMM

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

HSSC Cable

GND

T1

WATER POF 1

BIN6

COM

E

LEAVING WATER
TEMPERATURE 1

T2

BIN7

WATER POF 2

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

SUCTION PRESSURE
TRANSDUCER 1

SUCTION PRESSURE
TRANSDUCER 2

AOUT1

AOUT3

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

WattMaster Label

#S

000063

Rev.: 1B

W

E-BUS

HSSC

CONNECT

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHP-X2 WSHP-X2 MODULE

AAON NO.: V48820

+24 V

A

C

GND

www.orioncontrols.com

www.aaon.com

- COMP A1 EN

- HEAT ENABLE

- COMP A2 EN

- H2O POF A

- COMP B1 EN

- H2O POF B

- COMP B2 EN

- COMMON

GND

- LEAVING WATER TEMP

- GROUND

- LEAVING WATER TEMP

AOUT1

- COMP A1

DIGITAL/VFD COMPRESSORS

A1, A2, B1, B2

RELAY CONTACT RATING

IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5

RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO
CNTLR C2
TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

AOUT2

- COMP A2

AOUT3

- COMP B1

AOUT4

- COMP B2

E-BUS

HSSC

CONNECT

BIN1

BIN2

BIN3

BIN4

BIN5

BIN6

BIN7

COM

T 1

T 2

Compressor 1

Compressor 2

COM

+

COM

+

LEAVING WATER
TEMPERATURE 2

RNE 55 - 105 Ton Unit Compressor and Condenser Wiring

Figure 33: RNE 55 - 105 Ton Unit Two Compressor WSHP-X2 Wiring

WSHP-X2 Module

RNE Units with DX Cooling will have either a Half VFD/Half Fixed
compressor confi guration or a Full VFD compressor confi guration. The
RNE 55 - 105 Ton units have two compressors and will have either one
VFD and one Fixed Compressor or will have two VFD Compressors.
The operation of these compressors is described in the Sequence of
Operation section of this manual.

On Water Source Heat Pump (WSHP) units, the outputs to the compres-
sors will always be wired from the WSHP-X2 Module. Each compressor
will need to have a relay confi gured and wired from this module, and the
VFD output(s) will be wired from this module. The Suction Pressure
Transducer for each compressor and the Proof of Flow switch for each
water circuit will also be wired into this module. See Figure 33 below
for the wiring diagram. The WSHP-X2 Module monitors conditions on
the unit and can disable compressors based on Low Suction Pressure,
Low Leaving Water Temperature, or a loss of Water Proof of Flow. It
also utilizes a Delay Timer to prevent the compressors from turning on
at the same time.

The WSHP-X2 Module connects to the RNE Controller or the Two
Condenser Head Pressure II Module with an HSSC Cable. This allows
setpoints, status values, and alarms to be communicated between the
RNE Controller and the WSHP-X2 Module. This module requires a 24
VAC power connection with an appropriate VA rating.

NOTE: The Compressor Relays on the WSHP-X2 Module are

used rather than the relay outputs on the RNE
Controller.

NOTE: For more information, see the WSHP-X2 Module Field

Technical Guide.