Installation and wiring, Rne modular controller field technical guide, Full digital module – Orion System RNE Modular Controller User Manual

Page 43

Advertising
background image

RNE Modular Controller Field Technical Guide

INSTALLATION AND WIRING

43

AO1

AO2

+5V

SIG 2

GND

OPTI

O

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

OE370-23-FD-A

Full Digital Module

This Dip

Switch Is Not

Used For This

Application

This Dip

Switch Is Not

Used For This

Application

PWR

Connect To

RNE Controller

Connect To

Head Pressure Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result in
damage to the boards.

HSSC Cable

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER

ALL RELAY OUTPUTS

ARE

COMPRESSOR 3 ENABLE

COMPRESSOR 1 ENABLE

R1

R4

R3

R2

COMPRESSOR 2 ENABLE
COMPRESSOR 4 ENABLE

ONLY.

1 AMP MAXIMUM LOAD.

HVAC UNIT CONNECTIONS

SIG 1

GND

+V

BK

RD
WH

OE275-01 Suction

Pressure Transducers 1 - 4

AO1

O

SIG 2

GND

+V

BK

RD
WH

SIG 3

GND

+V

BK

RD
WH

SIG 4

GND

+V

BK

RD
WH

Compressor 1

Compressor 2

COM

+

COM

+

Compressor 3

Compressor 4

COM

+

COM

+

GND

1

3

2

4

RNE 120 - 140 Ton Unit Compressor and Condenser Wiring

Figure 35: RNE 120 - 140 Ton Unit Four Compressor Full Digital Module Wiring

Full Digital Module

RNE Units with DX Cooling will have either a Half VFD/Half Fixed
compressor confi guration or a Full VFD compressor confi guration. The
RNE 120 - 140 Ton units have four compressors and will have either
two VFD and two Fixed Compressors or will have four VFD Compres-
sors. The operation of these compressors is described in the Sequence
of Operation section of this manual.

If this is not a Water Source Heat Pump unit, the outputs to the com-
pressors will always be wired from the Full Digital Module ( OE370-
23-FD-A). Each compressor will need to have a relay confi gured and
wired from this module, and the VFD output(s) will be wired from this
module. Each compressor will also have a Suction Pressure Transducer
wired into this module. See Figure 35 below for the wiring diagram.

On units confi gured for Half VFD/Half Fixed operation, the two VFD
Compressors will both be driven from Analog Output (AO) #1, although
the individual compressor relays will be enabled separately as needed.

On units confi gured for Full VFD operation, the 1st two VFD Compres-
sors will be driven from AO #1 and the 2nd two VFD Compressors
will be driven from AO #2, although all four compressor relays will be
enabled separately as needed.

The Full Digital Module connects to the RNE Controller or a Two
Condenser Head Pressure Module with an HSSC Cable. This allows
setpoints, status values, and alarms to be communicated between the
RNE Controller and the Full Digital Module. This module requires a
24 VAC power connection with an appropriate VA rating.

NOTE: The Compressor Relays on the Full Digital Module

are used rather than the relay outputs on the RNE
Controller.

NOTE: For more information, see the Full Digital Module

Technical Guide found on our website orioncontrols.
com.

Advertising