RNE CONTROLLER TROUBLESHOOTING

RNE Modular Controller Field Technical Guide

70

Using LEDs To Verify Operation

The RNE Controller is equipped with 4 LEDs that can be used as very
powerful troubleshooting tools. See Figure 40 below for the LED loca-
tions. The LEDs and their uses are as follows:

REC

- This LED will light up to indicate system communications.

POWER

- This LED will light up to indicate that 24 VAC power has

been applied to the controller.

STATUS 1

- This is the diagnostic blink code LED. It will light up

and blink out diagnostic codes. STATUS 1 LED also represents the tens
column in the address blink code.

STATUS 2

- This is the diagnostic blink code LED. It will light up and

blink out diagnostic codes. STATUS 2 LED also represents the ones
column in the address blink code.

POWER LED Operations

When the RNE Controller is powered up, the POWER LED should light
up and stay on continuously. If it does not light up, check to be sure that
you have 24 VAC connected to the controller, that the wiring connec-
tions are tight, and that they are wired for the correct polarity. The 24
VAC power must be connected so that all ground wires remain common.
If after making all these checks, the POWER LED does not light up,
please contact WattMaster Controls Technical Support for assistance.

REC LED Operations

When power is applied to the controller, the REC LED will also light up.
If this is a Stand Alone System (one controller only on the loop) or an
Interconnected System (several RNE Controllers tied together without
a CommLink), the REC LED will glow continuously. The REC LED
will fl icker when you are connected to the RNE Controller and you are
entering setpoints with the Modular Service Tool or one of the System
Managers. It will also fl icker if this is a Networked System. If this is a
Networked System (the system has a CommLink installed), the REC

LED should fl icker rapidly, indicating that the system is communicat-
ing. A “fl icker” is defi ned as a brief moment when the LED turns off
and then back on. It may be easier to see this “fl icker” if you cup your
hand around the LED.

If the REC LED does not operate as indicated above, fi rst check the
address switch setting. Verify the address switch as outlined in the Di-
agnostic LEDs Operations section on page 71. See Figure 38 on page
48
for complete address switch setting instructions.

NOTE: STATUS 1 LED represents the tens position and STATUS

2 LED represents the ones position of the controller ad-
dress. If the address of the controller is set to 59 with the
address switch, fi rst STATUS 1 LED will blink 5 times,
and then STATUS 2 LED will blink 9 times.

If the address switch setting is correct and the REC LED still does not
behave as indicated above, check to be sure the operator’s interface is
connected correctly. If you are using the Modular Service Tool, verify
that it is plugged in securely to the DIN connection on the RNE Control-
ler. If you are using one of the System Manager Operator’s Interfaces,
see the RNE Controller Operator Interfaces Technical Guide or the
System Manager TS Operator Interfaces Technical Guide for a con-
nection diagram.

If the REC LED still does not behave correctly, check the voltages at
the communications terminal block. Be sure the Controller is powered
up for this test. Unplug the communications terminal block from the
controller and check the DC voltage between T and SHLD and between
R and SHLD. Check the voltage with a digital multimeter set to DC
volts. The voltage should be between 3.0 to 3.2 VDC between SHLD
and either T or R. If the voltage is not in this range, you probably have
a damaged driver chip that must be replaced.

For driver chip replacement instructions, contact the factory for further
assistance.

LED Diagnostics

RS-485
Communications
Driver Chip

Communications
LED

POWER LED

Diagnostic
Blink Code
LEDs
STATUS 1
STATUS 2

Relay Output
LEDS - Typ. of 5

10A250VAC ~

5A30VDC

SA

VDE

G5Q-1A4

OMRON

DC24V

CHINA

10A250VAC ~

5A30VDC

SA

VDE

G5Q-1A4

OMRON

DC24V

CHINA

10A250VAC ~

5A30VDC

SA

VDE

G5Q-1A4

OMRON

DC24V

CHINA

10A250VAC ~

5A30VDC

SA

VDE

G5Q-1A4

OMRON

DC24V

CHINA

10A250VAC ~

5A30VDC

SA

VDE

G5Q-1A4

OMRON

DC24V

CHINA

Figure 40: RNE Controller Diagnostic LED Locations

Advertising