INSTALLATION AND WIRING

45

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

HSSC Cable

Connect To Two Condenser Head

Pressure II Module

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHP-X2

Water Source

Heat Pump X2 Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. 4 ENABLE

COMP. 3 ENABLE

R1

R5

R3

COMM

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

HSSC Cable

GND

T1

WATER POF 3

BIN6

COM

E

LEAVING WATER
TEMPERATURE 3

T2

BIN7

WATER POF 4

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

SUCTION PRESSURE
TRANSDUCER 3

SUCTION PRESSURE
TRANSDUCER 4

AOUT1

AOUT3

WattMaster Label

#S

000063

Rev.: 1B

W

E-BUS

HSSC

CONNECT

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHP-X2 WSHP-X2 MODULE

AAON NO.: V48820

+24 V

A

C

GND

www.orioncontrols.com

www.aaon.com

- COMP A1 EN

- HEAT ENABLE

- COMP A2 EN

- H2O POF A

- COMP B1 EN

- H2O POF B

- COMP B2 EN

- COMMON

GND

- LEAVING WATER TEMP

- GROUND

- LEAVING WATER TEMP

AOUT1

- COMP A1

DIGITAL/VFD COMPRESSORS

A1, A2, B1, B2

RELAY CONTACT RATING

IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5

RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO
CNTLR C2
TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

AOUT2

- COMP A2

AOUT3

- COMP B1

AOUT4

- COMP B2

E-BUS

HSSC

CONNECT

BIN1

BIN2

BIN3

BIN4

BIN5

BIN6

BIN7

COM

T 1

T 2

Compressor 3

Compressor 4

COM

+

COM

+

LEAVING WATER
TEMPERATURE 4

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

HSSC Cable

Connect To Two Condenser Head

Pressure II Module

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHP-X2

Water Source

Heat Pump X2 Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

R1

R5

COMM

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

HSSC Cable

GND

T1

BIN6

COM

E

T2

BIN7

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

WattMaster Label

#S

000063

Rev.: 1B

W

E-BUS

HSSC

CONNECT

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHP-X2 WSHP-X2 MODULE

AAON NO.: V48820

+24 V

A

C

GND

www.orioncontrols.com

www.aaon.com

- COMP A1 EN

- HEAT ENABLE

- COMP A2 EN

- H2O POF A

- COMP B1 EN

- H2O POF B

- COMP B2 EN

- COMMON

GND

- LEAVING WATER TEMP

- GROUND

- LEAVING WATER TEMP

AOUT1

- COMP A1

DIGITAL/VFD COMPRESSORS

A1, A2, B1, B2

RELAY CONTACT RATING

IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5

RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO
CNTLR C2
TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

AOUT2

- COMP A2

AOUT3

- COMP B1

AOUT4

- COMP B2

E-BUS

HSSC

CONNECT

BIN1

BIN2

BIN3

BIN4

BIN5

BIN6

BIN7

COM

T 1

T 2

COM

+

COM

+

Figure 36, cont.: RNE 120 - 140 Ton Unit Four Compressor WSHP Module Wiring

The WSHP-X2 Module monitors conditions on the unit and can dis-
able compressors based on Low Suction Pressure, Low Leaving Water
Temperature, or a loss of Water Proof of Flow. It also utilizes a Delay
Timer to prevent the compressors from turning on at the same time.

The WSHP Modules connect together and then connect back to the RNE
Controller or the Two Condenser Head Pressure Modules with HSSC
cables. This allows setpoints, status values, and alarms to be communi-
cated between the RNE Controller and the WSHP Module. This module
requires a 24 VAC power connection with an appropriate VA rating.

NOTE: The Compressor Relays on the WSHP Module are used

rather than the relay outputs on the RNE Controller.

NOTE: For more information, see the WSHP-X2 Module Field

Technical Guide.

RNE 120 - 140 Ton Unit Compressor and Condenser Wiring