Installation and wiring, Rne modular controller field technical guide, Title 24 economizer actuator feedback – Orion System RNE Modular Controller User Manual

Page 33: Building pressure sensor

Advertising
background image

RNE Modular Controller Field Technical Guide

INSTALLATION AND WIRING

33

Title 24 Economizer Actuator Feedback & Building Pressure Sensor

Title 24 Economizer Actuator

Feedback

If the controller has been confi gured for Title 24 Economizer operation,
the Economizer Actuator Feedback signal is wired to the AI3 input on
the VCM-X Expansion Module. It must be wired as shown in Figure
24
below for proper controller operation.

Warning: It is very important to be certain that all wiring is cor-
rect as shown in the wiring diagram below. Failure to observe the
correct polarity will result in damage to the HVAC Unit Controller
and the VCM-X Expansion Module.

Figure 24: Title 24 Economizer Actuator Feedback Wiring

AI3

GND

To GND

Jumper Must

Be Set To

0-10V As Shown

VCM-X Expansion

Module

Title 24 Economizer

Actuator Feedback

Signal 0-10VDC

(By Others)

Economizer Damper Actuator

(Belimo Actuator Shown)

Y1 3

+ 2

COM - 1

Economizer Feedback 5

Belimo Actuator Wiring

Shown. Consult Factory

For Other Manufacturer

Wiring Instructions

NOTE: For Economizer

Actuator Wiring, See

Wiring For The

RNE Controller.

AO1

See Economizer
Actuator Wiring

For RNE

Controller

AO1

Building Pressure Sensor

The OE258-01 Building Pressure Sensor must be wired as shown in the
illustration below for proper operation. There are 3 terminal connections
on the Building Pressure Sensor. Connect the power side of the 24 VAC
power source to the terminal labeled “+ EXC.” Connect the GND side
of the 24 VAC power source to the terminal labeled “- COM.” Connect
the remaining terminal labeled “OUT” to AI4 on the VCM-X Expansion
Module terminal block. See Figure 25 below for detailed wiring. The
AI4 Jumper on the expansion module must be set for 0-5VDC operation
for the Building Pressure Sensor to operate correctly.

AI4

GND

Jumper Must

Be Set To

0-5V As Shown

EXC

COM

OUT

LOW

-

+

+

+

Tubing To Building
Pressure Sensing Location

Tubing To Atmospheric
Pressure Sensing Location

-

+

Building Pressure Sensor

HIGH

VCM-X Expansion

Module

To

GND

24

VAC

Figure 25: OE258-01 — Building Pressure Sensor Wiring

Advertising