Zone

Zone

INSTALLATION AND WIRING

RNE Modular Controller Field Technical Guide

42

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers 1 - 2

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP2C2

Two Condenser Head Pressure II Module

OPTIONS Dip Switch Setting Not

Required When Connected To

RNE Controller.

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

Connect To

Full Digital Module

or WPM Module

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

HSSC Cable

Set ADDRESS Dip Switch 1 to ON for

Water Cooled or to OFF for Air Cooled.

Currently showing OFF.

Set ADDRESS Dip Switch 2 to OFF.

Currently showing OFF.

ADDRESS Dip Switch 3 should always

be set to OFF. Currently showing OFF.

Set ADDRESS Dip Switch 4 to OFF to

make reversing valve "ON to Heat /

OFF to Cool.” Set to ON to make

reversing valve “ON to Cool / OFF to

Heat.” Currently showing OFF.

BIN 1

BIN 2

BIN 3

COM

COM

+

Condenser

Signal 2

COM

+

Condenser

Signal 1

CONDENSER 1 ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER 2 ENABLE

COMM

REVERSING VALVE 2 ENABLE

REVERSING VALVE 1 ENABLE

R4

R2

+24 Volts

Condenser Fan 1

ECM Motor

Duty Cycle

Condenser Fan 2

ECM Motor

YELLOW

BLUE +24 OUT

+24 Volts

Duty Cycle

YELLOW
BLUE +24 OUT

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL
COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2

RNE 55 - 105 Ton Unit Compressor and Condenser Wiring

Figure 34: RNE 55 - 105 Ton Unit Two Compressor Two Condenser Head Pressure II Module Wiring

Two Condenser Head Pressure II

Module

For RNE 55 - 105 Ton units, the Two Condenser Head Pressure II Module
( OE370-23-HP2C2) will monitor two head pressure transducers and
control two condenser fans or water valves. A pulse width modulation
(PWM) signal or a 0-10 VDC output signal is used to control these
condenser devices. See Figure 34 below for the wiring diagram.

The Two Condenser Head Pressure II Module connects to the Full Digital
Module, the Water Source Heat Pump Module, or the RNE Controller
with an HSSC cable. This allows setpoints, status values, and alarms to
be communicated between the RNE Controller and the Two Condenser
Head Pressure II Module. This module requires a 24 VAC power con-
nection with an appropriate VA rating.

NOTE: For more information, see the Two Condenser Head

Pressure Module II Technical Guide found on our
website orioncontrols.com.