5-9 Restoring the Controller to Factory Setup

If the controller pre-set parameters have been tampered with and it no longer controls
temperature properly, restore the factory setup using these procedures:

1. Turn off the power switch on the graphic display and remove all electrical power to the

dryer.

2. Press up the latch at the bottom of the control module front panel and slide out the control

chassis.

3. Locate the slide-type lockout switch marked

SW101 {PROTECT}

on the left circuit board. It should be

OFF

.

4. Make sure the control output relays are installed on the right-hand circuit board. Your

unit uses one E53-S solid state relay (SSR) mounted in the socket marked

S201 (HEAT)

.

This relay switches the heater on and off.

5. Set the output selector switch marked

SW202

to

PULSE

. This slide-

type switch is near the control output socket.

6. Set the rotary-type alarm mode selector switch marked

SW205

to Position

2

for

upper limit alarm only.

7. Set the rotary-type ALM2 switch marked

SW203

to Position

0

, the No Alarm

function.

8. Set the rotary temperature sensor selector switch to Position

2

. It is marked

SW206 (INPUT TYPE)

and is on the right-hand circuit board.

Your unit is factory-equipped with Type K thermocouples; six (6) other
temperature sensor types can be used if the switch is properly set.

9. Set both transmission output selector DIP switches to

OFF

. They are marked

SW207

(TRANSFER)

and are on the right circuit board on controls equipped with optional

communications. See the Communications Manual (AEC Part No. A0535959) for more
information.

10. The function selector DIP switch marked

SW201 (FUNCTION)

selects six control modes.

It is located on the right-hand circuit board. Put this switch in the setup configuration (see
the table below) when you enter the initial control parameters.

SW201 Setup Configuration

Switch Position

Description

1 OFF

Control

mode

2 OFF

Normal/reverse

output

3 OFF

Input

shift

4

OFF

Temperature sensor standard

5

ON

Scale indication — ºF

6

ON

PID constant indication

OFF

ON

SW101 {PROTECT}

OFF

ON

PUL-CUR

0

1

2

3

4

5

6

7

8

9

SW205

0

1

2

3

4

5

6

7

8

9

SW203 [ALM]

0

1

2

3

4

5

6

7

8

9

SW206 (INPUT TYPE)