SMA STP 10000TL-10 Installation User Manual

Page 106

Advertising
background image

14  Technical Data

SMA Solar Technology AG

106

STP10-17TL-IA-en-32

Installation Manual

AC Output

* Depending on country setting

Protective Devices

Rated power at 230 V, 50 Hz

17,000 W

Maximum apparent AC power cos φ = 1

17,000 VA

Rated grid voltage

3/N/PE, 230 V/400 V

AC voltage range*

160 V to 280 V

Nominal AC current at 230 V

24.6 A

Maximum output current

24.6 A

Maximum output current in the event of an error

0.05 kA

Total harmonic factor of output current at
AC voltage < 2% and AC power > 0.5% of
nominal AC power

≤ 2.6%

Maximum residual output current

96 mA

Rated mains frequency

50 Hz

AC power frequency**

50 Hz/60 Hz

Operating range at AC mains frequency 50 Hz

44 Hz to 55 Hz

Operating range at AC mains frequency 60 Hz

54 Hz to 65 Hz

Displacement power factor, adjustable

0.8

overexcited

to 1 to 0.8

underexcited

Feed-in phases

3

Connection phases

3

Overvoltage category as per IEC 60664-1

III

DC reverse polarity protection

Short-circuit diode, electronic string fuse

Protection against module reverse currents

Electronic string fuse

Input-side disconnection device

Electronic Solar Switch, SUNCLIX DC connector

DC overvoltage protection

Thermally monitored varistors

optional: surge arrester type II

AC short-circuit current capability

Current control

Grid monitoring

SMA Grid Guard 4

Maximum permissible fuse protection

50.0 A

Earth fault monitoring

Insulation monitoring R

iso

> 323.4 k Ω

All-pole sensitive residual-current monitoring unit

available

String-failure detection

available

Advertising
This manual is related to the following products: