6  Electrical Connection

SMA Solar Technology AG

40

STP10-17TL-IA-en-32

Installation Manual

6.4.4 Connecting the PV Array (DC)

Danger to life due to high voltages in the inverter

• Before connecting the PV array, ensure that the AC miniature circuit-breaker is switched off for

all three phase conductors.

Risk of electric arc if the DC connectors are pulled out while the Sunny Tripower is
beeping
The integrated electronic string fuse monitors the PV array. In case of incorrect installation
(e.g. reverse polarity) or a faulty string, the electronic string fuse short-circuits the PV array and the
Sunny Tripower starts to beep.

• Do NOT pull the DC connector out as this could trip an electric arc.
• Do NOT pull out the Electronic Solar Switch as otherwise the entire reverse current will flow

through the defective string which could result in a fire.

• Further procedure (see Section 12.1 "Sunny Tripower is Beeping", page 82).

Destruction of the inverter due to overvoltage
If the voltage of the PV modules exceeds the maximum input voltage of the inverter, it could be
destroyed by overvoltage. This will void all warranty claims.

• Do not connect any strings to the inverter which have an open-circuit voltage greater than the

maximum input voltage of the inverter.

• Check the system design.

Excessive voltages can destroy the multimeter

• Only use multimeters with a DC input voltage range up to at least 1,000 V.