14  Technical Data

Installation Manual

STP10-17TL-IA-en-32

93

* Depending on country setting

Protective Devices

General Data

Rated mains frequency

50 Hz

AC mains frequency*

50 Hz/60 Hz

Operating range at AC mains frequency 50 Hz

44 Hz to 55 Hz

Operating range at AC mains frequency 60 Hz

54 Hz to 65 Hz

Displacement power factor, adjustable

0.8

overexcited

to 1 to 0.8

underexcited

Feed-in phases

3

Connection phases

3

Overvoltage category as per IEC 60664-1

III

DC reverse polarity protection

Short-circuit diode, electronic string fuse

Protection against module reverse currents

Electronic string fuse

Input-side disconnection device

Electronic Solar Switch, SUNCLIX DC connector

DC overvoltage protection

Thermally monitored varistors

optional: surge arrester type II

AC short-circuit current capability

Current control

Grid monitoring

SMA Grid Guard 4

Maximum permissible fuse protection

50.0 A

Earth fault monitoring

insulation monitoring R

iso

> 550 k Ω

All-pole sensitive residual-current monitoring unit

available

String-failure detection

available

Width x height x depth with
Electronic Solar Switch

665 mm x 690 mm x 265 mm

Weight

59 kg

Length x width x height of packaging

780 mm x 380 mm x 790 mm

Transport weight

65 kg

Climatic class in accordance with
IEC 60721-3-4

4K4H

Environment category

Outdoors

Degree of pollution outside the enclosure

3

Degree of pollution inside the enclosure

2