SMA STP 10000TL-10 Installation User Manual

Page 36

Advertising
background image

6  Electrical Connection

SMA Solar Technology AG

36

STP10-17TL-IA-en-32

Installation Manual

• The following thresholds at the DC input of the inverter must not be exceeded:

• On the coldest day based on statistical records, the open-circuit voltage of the PV array must

never exceed the maximum input voltage of the inverter.

Use of Y adaptors for the parallel connection of strings

Y adaptors must not be visible or freely accessible in close proximity to the inverter.

• The DC electric circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter (see Section 9 "Disconnecting the

Inverter from Voltage Sources", page 61).

Sunny
Tripower

Maximum input voltage

(DC)

Maximum input current

(MPP) (DC)

Maximum

short-circuit current per

string input (DC)

Input area A/B

A1 to A5 / B

10000TL

1,000 V

22.0 A / 11.0 A

33 A / 12.5 A

12000TL

1,000 V

22.0 A / 11.0 A

33 A / 12.5 A

15000TL

1,000 V

33.0 A / 11.0 A

40 A / 12.5 A

17000TL

1,000 V

33.0 A / 11.0 A

40 A / 12.5 A

Risk of fire as a result of overcurrent on the string input
Destruction of the inverter
Since the electronic string fuse shorts the PV array in the event of a fault, the thresholds for the
maximum short-circuit current per string input given in the table above must not be exceeded.
If a string input is overloaded, it can result in an electric arc and hence a risk of fire.

• Make sure that the thresholds specified in the table above are not exceeded.
• Check whether the short-circuit currents of the connected PV modules are in compliance with

the thresholds given in the table above.

Advertising
This manual is related to the following products: