6  Electrical Connection

Installation Manual

STP10-17TL-IA-en-32

35

6.4 Connecting the PV Array (DC)

6.4.1 Conditions for DC Connection

The inverter has two input areas "A" and "B", each with its own MPP tracker.

Up to four strings (Sunny Tripower 10000TL / 12000TL) or five strings (Sunny Tripower 15000TL /
17000TL) can be connected at input area A. One string can be connected at input area B.

• For input area A, the PV modules must meet the following requirements:

– same type
– same number of in-series-connected PV modules
– identical alignment
– identical tilt

• For the activation of the intelligent string failure detection, the PV modules at input A and B must

be identically aligned.

• The connecting cables of the PV modules must be equipped with connectors. The connectors

required for DC connection are included in the scope of delivery.