MotionSuite™ MP940 Machine Controller Hardware Manual

Section 5: Communications

30

Setting the Network Address

There are two rotary switches on the side of the MP940D. Rotate the switches to the
appropriate node address. Every device on the network must have a unique address.
For example, to set the unit to address 46, set the left dial to “4” and the right dial to
“6” as shown below. Note: The maximum number of device nodes is 63.

Setting the Baud Rate

There are four DIP switches on the side of the unit.

Follow the chart to set each of the baud rates.

DR1

DR0

125k

OFF

OFF

250k

OFF

ON

500k

ON

OFF

Figure 5.9: Rotary Switches

0

5

1

2

3

4

6

7

8

9

0

5

1

2

3

4

6

7

8

9

×10

×1

ON

1

2

3

4

X2 X1 DR1 DR0

ON

1

2

3

4

X2 X1 DR1 DR0

X2

not used

X1

OFF SLAVE
ON MASTER

DR1

baud

DR0

baud

Figure 5.10: DIP Switches