MotionSuite™ MP940 Machine Controller Hardware Manual

Section 5: Communications

35

„

Slave

Troubleshooting Slaves

Indicators

Problem

Probable Cause

Possible Solution

MS not lit
NS lit

No DeviceNet
communica-
tions

No power
supply to
MP940D

Check the network power supply to the MP940D.

MS red lit
NS not lit

Hardware
malfunction

Replace the MP940D.

MS red lit
NS red lit

Hardware
malfunction

Replace the MP940D.

MS green lit
NS red lit

Duplicate
MAC ID

(1) Change the MAC ID address for the MP940D and
cycle the power
(2) Change the MAC ID addresses for other DeviceNet
devices and cycle the power to the MP940D.

Bus-OFF

(1) Check the wiring and connections for DeviceNet
cables and connectors.
(2) Check the power supply voltage and connections for
communications power.
(3) Check for network power supply voltage on the
DeviceNet connector of the MP940D (11 to 24V).
(4) Check the baud rate for each DeviceNet device on the
network.
(5) Check the terminator (121

Ω) and connection status.

(6) Check the length of the network.
(7) Replace the MP940D. Then, either cycle the power
for the MP940D or disconnect and reinsert the DeviceNet
connectors.

MS green lit
NS not lit

Communica-
tions power
supply error

(1) Check the wiring and connections for DeviceNet
cables and connectors.
(2) Check the power supply voltage and connections for
network power.
(3) Check the communications power supply voltage on
the DeviceNet connector of the MP940D (11 to 24V).
(4) Check the terminator (121

Ω) and connection status.

MS red lit
NS not lit

DeviceNet
network error

(1) Check the wiring and connections for DeviceNet
cables and connectors.
(2) Check the baud rate for each device.
(3) Check the terminator (121

Ω) and connection status.

(4) Check the operation status of the DeviceNet master.
(5) Replace the MP940D.

MS green lit
NS green flash-
ing

Connection not
established
with
DeviceNet
device

(1) Check the DeviceNet master scan list settings.
(2) Check the wiring and connections for DeviceNet
cables and connectors.
(3) Check the baud rate for each device.
(4) Check the operation status of the DeviceNet master.