6 Procedure A

26

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

8.

Loosen the screws attaching the NEMA Type 1 conduit bracket to the drive to
remove the NEMA Type 1 conduit bracket.

Figure 14

Figure 14 Remove the NEMA Type 1 Conduit Bracket

9.

Select one of the four different length ground wires packaged with the option,

Figure 15

. Choose the proper ground wire by first removing the ground terminal

screw from the drive

Figure 16

. Test fit the screw (size M3.5 to M6) into each of the

four ground drive-side ring lugs prior to installation. Ground wire selection varies by

drive model.

Figure 15

Figure 15 Ground Wire Selection

To Option ground screw FE
Screw size: M3

To drive ground terminal
Screw size: M3.5 to M6