11 Troubleshooting

60

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

LED Operator Display

Fault Name

EF0

External Fault Input from the option.
The alarm function for an external device is triggered.

Cause

Corrective Action

An external fault is being sent from
the upper controller (PLC).

Remove the cause of the external fault
Reset the external fault input from the PLC device

Problem with the PLC program.

Check the program used by the PLC and make the appropriate corrections.

LED Operator Display

Fault Name

oFA00

Option Fault.
Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to
the drive.

Connect an option that is compatible with the drive.

LED Operator Display

Fault Name

oFA01

Option Fault.
Option is not properly connected.

Cause

Possible Solution

Problem with the connectors between
the drive and option.

Turn the power off and check the connectors between the drive and option.

LED Operator Display

Fault Name

oFA03

Option Fault.
Option self-diagnostics error.

Cause

Possible Solution

Option hardware fault.

Replace the option.

LED Operator Display

Fault Name

oFA04

Option Fault.
Option Flash write mode.

Cause

Possible Solution

Option hardware fault.

Replace the option.