7 Procedure B

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

37

8.

Pass the ground wire into the through-hole for ground wire, in the back of the option,
and connect the ground wire at the option ground terminal (FE). Tighten the screw

to 0.5 ~ 0.6 Nm or (4.4 ~ 5.3 in lbs) using an M3 Phillips screwdriver.

Figure 32

Figure 32 Ground Wire Connection Option Unit Side

9.

Firmly connect RJ45 8-pin Shielded Twisted Pair Cat5e cable(s) into the modular
connector ports to connect the option to a network,

Figure 33

.

Refer to Network

Topology and Connections on page 41

.

NOTICE: Do not connect or disconnect the communication cable while the drive is powered up or while the

drive is in operation. Failure to comply may cause a static discharge, which will cause the option card to stop

working properly. Cycle power on the drive and option card to attempt to reestablish functionality.

Figure 33

Figure 33 Communication Cable Ports

Option unit ground
terminal (FE)

Ground terminal
screw

Ground wire

Option through-hole
for ground wire

Option back side

Ground wire to
drive ground terminal
screw

RJ45 8-pin Shielded Twisted Pair
Cat5e cable(s)