11 Troubleshooting

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

61

Minor Faults and Alarms

LED Operator Display

Fault Name

to

oFA30 to oFA43

Option Fault (Port A).

Communication ID error.

Cause

Possible Solution

Option hardware fault.

Replace the option.

LED Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error.
Communication is not established.

Cause

Possible Solution

Minor Fault

(H2- = 10)

Communication wiring is faulty, there
is a short circuit, or improper
connection.

Check for wiring errors
Correct the wiring
Remove ground shorts and reconnect loose wires

YES

Programming error on the master side.

Check communications at start-up and correct
programming errors.

Communication circuitry is damaged.

Perform a self-diagnostics check
Replace the drive if the fault continues to occur