11 troubleshooting – Yaskawa V1000-Series Option SI-EP3/V PROFINET User Manual

Page 63

Advertising
background image

11 Troubleshooting

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

63

Related Parameters

Table 15 Parameters related to bUS Error Auto-Reset Functionality

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive

digital operator as shown in

Table 16

.

Table 16 Option Fault Monitor Descriptions

No.

(Addr. Hex)

<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error is detected. Use caution and proper

safety measures, when installing an emergency stop switch.

<5> Available in drive software versions PRG:1024 and later when combined with option firmware version

VST800251 and later. Not available in drive software versions PRG:508.

Name

Description

Default

F6-01

(03A2)

Operation Selection after
Communications Error

Determines drive response when a bUS error is
detected during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<5>

5: Alarm Ramp to Stop

<5>

<6> Available in option firmware version VST800251 and later.

1

F6-14

<6>

(03BB)

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-16

<6>

(03F4)

Communication Loss Timeout

Sets the timeout value for communication loss
detection in tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0
seconds.
Note: A change to this parameter setting is not
effective until main power to the drive is cycled.

0.0

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults.

Force Fault

EF0

3

Network sent a message to force this node to the fault
state.

Network Link
Down

BUS ERROR

1300

No network link to option board.

Network Failure

BUS ERROR

1301

Connection with PLC Timeout.

Default MAC
Address

None

1303

Factory default MAC Address programmed into the
option. Return for reprogramming.

No IP Address

None

1304

No IP Address has been programmed into the option.

No Station Name

None

1305

No Station Name has been programmed into the option.