7 procedure b, Procedure b steps, Procedure – Yaskawa V1000-Series Option SI-EP3/V PROFINET User Manual

Page 33: From st, 7procedure b

Advertising
background image

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

33

7 Procedure B

7

Procedure B

Use Procedure B steps to install the option on drives with a NEMA Type 4X/IP66

enclosures or with the enclosure type digit G within the model number.

Procedure B Steps

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to

comply will result in death or serious injury. Before installing the option, disconnect all power to the drive.

The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED

will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes

after all indicators are off and measure the DC bus voltage level to confirm safe level.

NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling

the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.

1.

Shut off power to the drive, wait at least five minutes after confirming the DC bus
voltage is safe, then loosen the bolts that fasten the front cover in place and remove

the front cover.

2.

Press firmly on the connector release tab holding the LED operator cable (CN1) in
place and disconnect the cable.

Figure 26

Figure 26 Remove the Drive Front Cover

Remove LED operator cable

Connector release tab

Front cover

Front cover bolt

Drive

CN1 port

Advertising