11 Troubleshooting

62

YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual

bUS Error Auto-Reset

bUS Error Auto-Reset Function Description

bUS Error Auto-Reset when configured, allows the drive to automatically recover from a

bUS error as a result of a communication loss with the host.
A bUS Error will automatically reset under the following conditions.

• Network communication between the host and the drive is restored. (bUS error removed)

• bUS Error Auto-Reset is enabled as described in this section.

Enabling bUS Error Auto-Reset

Parameter F6-14

<1>

bUS Error Auto Reset enables the bUS Error Auto-Reset function. F6-

14 becomes available when the option is installed on the drive.

1. Set parameter F6-14 = 1:Enabled

2. Set parameter F6-01 = 0:Ramp to Stop, 1:Coast to Stop, 2:Fast-Stop

3. Set parameter F7-16 = 0.1 to 10.0 seconds (optional)
Enabling bUS Error Auto-Restart (After a Time Delay)

Parameter F7-16 Communication Loss Timeout will delay the occurance of a bUS error

condition by the amount of time set in this parameter. F7-16 is set in tenths of seconds. The

status LEDs on the option will indicate the bUS error condition immediately upon detection

and during the F7-16 delay time. Refer to

Figure 52

.

• Set parameter F7-16 = 0.1 to 10.0 seconds (0.0 setting disables F7-16) to enable timeout

delay.

Figure 52

Figure 52 bUS Error Delay Timing Example

<1>

Available in SI-EP3/V firmware version VST800251 and later when used with V1000 drive software versions

PRG:1024 and later.

E86

&RQGLWLRQ

E86 (UURU

RQ GULYH

2XWSXW

)UHTXHQF\

E86 (UURU 'HOD\

) !  &RPP/RVV 7RXW

1HWZRUN

FRQQHFWLRQ
LQWHUUXSWHG

1HWZRUN

FRQQHFWLRQ

UHWXUQV

)

 VHF

)

 VHF

)

 VHF