5-2 Setting GPD 515 Parameters for Communication

Run/Stop and Frequency Selection

The run/stop commands and frequency reference command can originate from serial
communication, the Digital Operator, the external terminals, or an option board. The origin of the
run/stop command does not have to be the same as the origin for the frequency reference
command. Parameter b1-01 (Reference Selection) allows you to set up the origin of the
frequency reference, and parameter b1-02 (Operatoin Mode Selection) sets the origin of the
run/stop commands. Parameter b1-01 is Modbus register number 180h, and b1-02 is Modbus
register 181h. The charts shown below illustrate the possible frequency reference and run/stop
selections.

Parameter b1-01 (180h)

Setting

Frequency Reference Selection

0

Digital Operator

1

External Terminals

2

Serial Communication

3

Option board

The default setting of parameter b1-01 is ë1í.

Parameter b1-02 (181h)

Setting

Operation Method Selection

(Run/Stop)

0

Digital Operator

1

External Terminals

2

Serial Communication

3

Option board

The default setting of parameter b1-02 is ë1í.