Drive Parameter Registers (Read/Write) (continued)

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

48Dh

L3-06

Stall Prevention Level during Running

30 to 200%

160

48E-48Fh

Reserved

490h

L4-01

Speed Coincidence Frequency

0.0 to 400.0 Hz

0.0

491h

L4-02

Speed Coincidence Width

0.0 to 20.0 Hz

2.0

492h

L4-03

Speed Coincidence Frequency (+/-)

-400.0 to +400.0 Hz

0.0

493h

L4-04

Speed Coincidence Width (+/-)

0.0 to 20.0 Hz

2.0

494h

L4-05

Frequency Reference Loss

0

Stop

0

Detection

1

Run at 80% of Frequency Reference

495h

L5-01

Number of Auto Restart Attempts

0 to 10

0

496h

L5-02

Auto Restart Operation Selection

0

No Fault Relay

0

1

Fault Relay Active

497h

L5-03

Fault Restart Time

0.5 to 180.0 seconds

10.0

498h

L6-01

Torque Detection Selection 1

0

Disabled

1

Detected during Speed Agree

(operation continues)

2

Detected during Running (operation

continues)

0

3

Detected during Speed Agree (drive

faults)

4

Detected during Running (drive faults)

499h

L6-02

Torque Detection Level 1

0 to 300%

150

49Ah

L6-03

Torque Detection Time 1

0.0 to 10.0 seconds

0.1

49Bh

L6-04

Torque Detection Selection 2

0

Disabled

1

Detected during Speed Agree

(operation continues)

2

Detected during Running (operation

continues)

0

3

Detected during Speed Agree (drive

faults)

4

Detected during Running (drive faults)