Yaskawa GPD 515-G5 Modbus RTU User Manual
Page 53

7-17
Registers
Drive Parameter Registers (Read/Write) (continued)
REGISTER
PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
300h
E1-01
Input Voltage Setting
155 to 255V (230V unit)
310 to 510V (460V unit)
230
460
301h
E1-02
Motor Selection
0
General Purpose Motor (TEFC)
0
1
Blower Cooled Motor (TENV or
TEBC)
302h
E1-03
V/f Pattern Selection
0 to Eh
15 preset V/f patterns
Fh
Custom Pattern (using E1-04 to
E1-10)
Fh
303h
E1-04
Maximum Ooutput Frequency
50.0 to 400.0 Hz
60.0
304h
E1-05
Maximum Voltage
0.0 to 255.0V (230V unit)
0.0 to 510.0V (460V unit)
230.0
460.0
305h
E1-06
Maximum Voltage Frquency
0.0 to 400.0 Hz
60.0
306h
E1-07
Mid. Output Frequency
0.0 to 400.0 Hz
(1)
307h
E1-08
Mid. Output Frqeuency Voltage
155 to 250V (230V unit)
310 to 510V (460V unit)
(1)
308h
E1-09
Min. Output Frequency
0.0 to 400.0 Hz
(1)
309h
E1-10
Min. Output Frequency Voltage
155.0 to 255.0V (230V unit)
310.0 to 510.0V (460V unit)
(1)
30Ah
E1-11
Mid. Frequency B
0.0 to 400.0 Hz
0.0
30Bh
E1-12
Mid. Voltage B
0.0 to 255.0 VAC
0.0
30Ch
E1-13
Base Voltage
0.0 to 255.0 VAC
0.0
30Dh
Reserved
30Eh
E2-01
Motor Rated Current
0.00 to 99.99 or 100.0 to 1500.0 Amps
(2)
30Fh
E2-02
Motor Rated Slip
0.00 to 20.00 Hz
(2)
310h
E2-03
Motor no-Load Current
0.00 to 99.99 or 100.0 to 1500.0 Amps
(2)
311h
E2-04
Number of Motor Poles
2 to 48 poles
4
312h
E2-05
Motor Line-to-Lline Resistance
0.000 to 65.000 Ohms
(2)
Notes (for this page only):
1. Initial value differs depending on the Control Method (A1-02).
2. Initial value differs depending on drive capacity.