Yaskawa GPD 515-G5 Modbus RTU User Manual

Page 53

Advertising
background image

7-17

Registers

Drive Parameter Registers (Read/Write) (continued)

REGISTER

PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

300h

E1-01

Input Voltage Setting

155 to 255V (230V unit)
310 to 510V (460V unit)

230
460

301h

E1-02

Motor Selection

0

General Purpose Motor (TEFC)

0

1

Blower Cooled Motor (TENV or

TEBC)

302h

E1-03

V/f Pattern Selection

0 to Eh

15 preset V/f patterns

Fh

Custom Pattern (using E1-04 to

E1-10)

Fh

303h

E1-04

Maximum Ooutput Frequency

50.0 to 400.0 Hz

60.0

304h

E1-05

Maximum Voltage

0.0 to 255.0V (230V unit)
0.0 to 510.0V (460V unit)

230.0
460.0

305h

E1-06

Maximum Voltage Frquency

0.0 to 400.0 Hz

60.0

306h

E1-07

Mid. Output Frequency

0.0 to 400.0 Hz

(1)

307h

E1-08

Mid. Output Frqeuency Voltage

155 to 250V (230V unit)
310 to 510V (460V unit)

(1)

308h

E1-09

Min. Output Frequency

0.0 to 400.0 Hz

(1)

309h

E1-10

Min. Output Frequency Voltage

155.0 to 255.0V (230V unit)
310.0 to 510.0V (460V unit)

(1)

30Ah

E1-11

Mid. Frequency B

0.0 to 400.0 Hz

0.0

30Bh

E1-12

Mid. Voltage B

0.0 to 255.0 VAC

0.0

30Ch

E1-13

Base Voltage

0.0 to 255.0 VAC

0.0

30Dh

Reserved

30Eh

E2-01

Motor Rated Current

0.00 to 99.99 or 100.0 to 1500.0 Amps

(2)

30Fh

E2-02

Motor Rated Slip

0.00 to 20.00 Hz

(2)

310h

E2-03

Motor no-Load Current

0.00 to 99.99 or 100.0 to 1500.0 Amps

(2)

311h

E2-04

Number of Motor Poles

2 to 48 poles

4

312h

E2-05

Motor Line-to-Lline Resistance

0.000 to 65.000 Ohms

(2)

Notes (for this page only):

1. Initial value differs depending on the Control Method (A1-02).
2. Initial value differs depending on drive capacity.