Simultaneous broadcast registers (write only) – Yaskawa GPD 515-G5 Modbus RTU User Manual

Page 38

Advertising
background image

7-2

Registers

Simultaneous Broadcast Registers (Write only)

REGISTER

FUNCTION

BIT

DATA

DESCRIPTION

(in hex)

NO.

SET

001*

Operational Signals

0

0

Stop

1

Run

1

0

Forward Run

1

Reverse Run

2

not used

3

not used

4

1

External Fault

5

1

Fault Reset

6

not used

7

not used

002*

Frequency Reference

Frequency Reference (6000 = 100%) (1)

Notes:

1. Scaling depends on the setting of o1-03.
* Set parameter o2-09 to ‘1’ so that the Modbus Register Address of the Operation Signals register is 01h and the Frequency Reference register is 02h. The

Modbus Register Address for Operation Signals register is 00h and the Frequency Reference is 01h for flash software versions previous to ‘1024’
and CPU version ‘20’.