7-9

Registers

Drive Parameter Registers (U2-XX / Fault Trace and U3-XX / Fault History)

REGISTER

PARAMETER

PARAMETER

PARAMETER

BIT

LIMITS / DESCRIPTION

(in hex)

FUNCTION

SETTING

NO.

080h

U2-01

Current Fault

Code of current fault (1)

081h

U2-02

Last Fault

Code of second to current fault (1)

082h

U2-03

Frequency Ref. at Fault

Frequency Reference at the time of the current fault (0.0 to 400.0 Hz)

083h

U2-04

Output Frequency at Fault

Output Frequency at the time of current fault (0.0 to 400.0 Hz)

084h

U2-05

Output Current at Fault

Output Current at the time of current fault (drive rating /8192)

085h

U2-06

Motor Speed at Fault

Motor Speed at the time of current fault (in 0.1 Hz)

086h

U2-07

Output Voltage at Fault

Output Voltage at the time of current fault (in 0.1 V)

087h

U2-08

DC Bus Voltage at Fault

Output Voltage at the time of current fault (in 1 V)

088h

U2-09

Output kWatts at Fault

Output Power at the time of current fault (in 0.1 kW)

089h

U2-10

Torque Reference at Fault

Torque Reference at the time of current fault (in 0.1%)

08Ah

U2-11

Input Terminal Status at Fault

0

Input Terminal 1 closed at time of fault

1

Input Terminal 2 closed at time of fault

2

Input Terminal 3 closed at time of fault

3

Input Terminal 4 closed at time of fault

4

Input Terminal 5 closed at time of fault

5

Input Terminal 6 closed at time of fault

6

Input Terminal 7 closed at time of fault

7

Input Terminal 8 closed at time of fault

08Bh

U2-12

Output Terminal Status at Fault

0

Control Circuit terminals 9 & 10: ìClosedî

1

Control Circuit terminals 25 & 27: ìClosedî

2

Control Circuit terminals 26 & 27: ìClosedî

3-6

not used

7

Control Circuit terminals 18 & 20: ìClosedî

Notes (for this page only):

1. List of Drive Error Codes can be found in Chapter 8, Error Codes and Troubleshooting.