Yaskawa GPD 515-G5 Modbus RTU User Manual

Page 56

Advertising
background image

7-20

Registers

Drive Parameter Registers (Read/Write) (continued)

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

38Dh

F2-01

AI-14 Bi-polar or Uni-polar Input

0

3-channel Individual

0

Selection

1

3-channel Addition

38Eh

F3-01

DI-16 Digital Input Option

0

BCD 1%

1

BCD 0.1%

2

BCD 0.01%

3

BCD 1 Hz

0

4

BCD 0.1 Hz

5

BCD 0.01 Hz

6

BCD (5DG) 0.01 Hz

7

Binary

38Fh

F4-01

AO-08/AO-12 Channel 1 Monitor Select.

1 to 33h (1)

2

390h

F4-02

AO-08/AO-12 Channel 1 Gain

0.00 to 2.50

1.00

391h

F4-03

AO-08/AO-12 Channel 2 Monitor Select.

1 to 33h (1)

3

392h

F4-04

AO-08/AO-12 Channel 2 Gain

0.00 to 2.50

0.50

393h

F5-01

DO-02 Channel 1 Output Selection

0 to Fh

0

394h

F5-02

DO-02 Channel 2 Output Selection

0 to Fh

1

395h

F6-01

DO-08 Output Mode Selection

0

8-channel Individual

0

1

Binary Output

396h

F7-01

PO-36F Frequency Multiple

Selection

0

1 x Output Frequency

1

6 x Output Frequency

2

10 x Output Frequency

1

3

12 x Output Frequency

4

36 x Output Frequency

Notes:

1. Range shown is for flash software version ‘1030’ and CPU version ‘30’. Range differs for previous versions.