7-25

Registers

Drive Parameter Registers (Read/Write) (continued)

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

49Ch

L6-05

Torque Detection Level 2

0 to 300%

150

49Dh

L6-06

Torque Detection Time 2

0.0 to 10.0 seconds

0.1

49Eh

L7-01

Forward Torque Limit

0 to 300%

200

49Fh

L7-02

Reverse Torque Limit

0 to 300%

200

4A0h

L7-03

Forward Regenerative Torque Limit

0 to 300%

200

4A1h

L7-04

Reverse Regenerative Torque Limit

0 to 300%

200

4A2-4A3h

Reserved

4A4h

L8-01

Internal Dynamic Braking

0

Not Provided

0

Resistor Protection

1

Provided

4A5h

L8-02

oH (Overheat) Protection Alarm Level

50 to 110

o

C

100

4A6h

L8-03

Operation Selection after oH

0

Ramp to Stop

(Overheat) Pre-alarm

1

Coast to Stop

3

2

Fast-stop

3

Alarm Only

4A7h

Reserved

4A8h

L8-05

Input Open-phase Protection

0

Disabled

0

Selection

1

Enabled

4A9h

Reserved

4AAh

L8-07

Output Open-phase Protection

0

Disabled

0

Selection

1

Enabled

4AB-4B1h

Reserved