7-26

Registers

Drive Parameter Registers (Read/Write) (continued)

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

500h

o1-01

Monitor Selection

4 to 28, 32, 33 (2)

6

501h

o1-02

Monitor Selection after Power-up

1

Frequency Reference

2

Output Frequency

1

3

Output Current

4

Selected Monitor

502h

o1-03

Digital Operator Display Selection

0 to 39999

0

503h

o1-04

Digital Operator Display Units

0

Hz

0

1

RPM

504h

o1-05

Parameter / Address Display

0

Parameter Number

0

Selection

1

Modbus Address

505h

o2-01

LOCAL / REMOTE Key

0

Disabled

1

Selection

1

Enabled

506h

o2-02

STOP Key Function during

0

Disabled

1

Remote Run

1

Enabled

507h

o2-03

User Parameter Default Value

0

Disabled

1

Set Default

0

2

Clear all

508h

o2-04

kVA Selection (Drive Model No.)

0 to FFh

(1)

509h

o2-05

Digital Operator

0

Drive accepts freq. after ENTER key

0

ìMotor Operated Potî

1

Drive accepts freq. immediately

Notes (for this page only):

1. Not initialized. Initial value differs depending on the drive capacity.
2. Range shown is for flash software version‘1030’ and CPU version ‘30’. Range differs for previous versions.