6-2 The Message Format

Message Functions

In communicating to the GPD 515 drive via Modbus RTU, there are three message functions
available. The master specifies the function to be executed by the slave according to the function
code. The following table shows the types of function codes available, and the length (quantity)
and contents of the message according to the function.

Function

Code (hex)

Function

Command

Message

Response

Message (Normal)

min.

(bytes)

max.

(bytes)

min.

(bytes)

max.

(bytes)

3

Read Multiple Registers

8

8

7

37

8

Loop-back test

8

8

8

8

10

Write Multiple Registers

11

41

8

8

The message format varies depending upon the function of the message. For each function,
there is a command message from the master and a response message initiated from the slave.
The following sections review the format of the command message and the response message
for each function.