6 Utility Functions (Fn

)

6-20

6

Press the

or

Key to adjust the offset

amount.
Adjust the offset amount by 10 in the direction that
the torque ripple is reduced.
Adjustment range: -512 to +511
(ZADJIV: Offset value of phase-V current)

Repeat the operations of steps 4 to 6 (phase-U and-V alternately) until adjusting the offset amounts both for
phase-U and -V in both directions cannot reduce the torque ripple any more.

Then, perform the same operation by adjusting by smaller amount.

7

Press the

Key to save the result of adjustment in

the SERVOPACK.
When the saving is completed, the status display

shows "DONE" for one second. The status display
then returns to show "RUN" again.

8

Press the

Key.

The display returns to the main menu of the utility

function.

(cont’d)

Step

Display after Operation

Keys

Operation

R U N
M a n u a l O f f s e t

− A D J

o f M o t o r C u r r e n t
Z A D J I U = - 0 0 0 1 9
Z A D J I V = - 0 0 0 1 6

R U N
M a n u a l O f f s e t

− A D J

o f M o t o r C u r r e n t
Z A D J I U = - 0 0 0 1 9
Z A D J I V = - 0 0 0 1 6

R U N

− F U N C T I O N −

F n 0 0 F : C u r M a n u A d j
F n 0 1 0 : P r m P r o t e c t
F n 0 1 1 : M o t o r I n f o
F n 0 1 2 : S o f t V e r