Yaskawa Sigma-5 Large Capacity Users Manual: Design and Maintenance-Rotary Motors-Mechatrolink-III Communication Reference User Manual

Page 333

Advertising
background image

9 Troubleshooting

9.1.2 Troubleshooting of Alarms

9-22

A.E72:
Feedback Option

Module Detection

Failure

The connection between the

SERVOPACK and the Feedback

Option Module is Faulty.

Check the connection between the

SERVOPACK and the Feedback

Option Module.

Correctly connect the Feedback

Option Module.

The Feedback Option Module
was disconnected.

Execute resetting configuration

error in option modules (Fn014) and

turn the power supply OFF and then

ON again.

A Feedback Option Module fault

occurred.

Replace the Feedback Option Mod-

ule.

A fault occurred in the SERVO-

PACK.

Replace the SERVOPACK.

A.E74:
Unsupported Safety

Option Module

A safety option module fault
occurred.

Replace the safety option module.

A unsupported safety option
module was connected.

Refer to the catalog of the con-
nected safety option module.

Connect a compatible safety option
module.

A.E75:
Unsupported

Feedback Option

Module

A feedback option module fault
occurred.

Replace the feedback option mod-
ule.

A unsupported feedback option
module was connected.

Refer to the catalog of the con-
nected feedback option module or
the manual of the SERVOPACK.

Connect a compatible feedback
option module.

A.EA2:
DRV Alarm 2
(SERVOPACK WDT
error)

MECHATROLINK transmission
cycle fluctuated.

Check the MECHATROLINK
transmission cycle setting.

Remove the cause of transmission
cycle fluctuation at host controller.

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.Eb1:
Safety Function Signal

Input Timing Error

The lag between activations of

the input signals /HWBB1 and

/HWBB2 for the HWBB function

is ten second or more.

Measure the time lag between the /

HWBB1 and

/HWBB2 signals.

The output signal circuits or devices

for /HWBB1 and

/HWBB2 or the SERVOPACK

input signal circuits may be faulty.

Alternatively, the input signal

cables may be disconnected. Check

if any of these items are faulty or

have been disconnected.

A.Ed1:
Command Execution

Timeout

A timeout error occurred when

using an MECHATROLINK
command.

Check the motor status when the
command is executed.

Execute the SV_ON or SENS_ON
command only when the motor is
not running.

For fully-closed loop control, check
the status of the external encoder
after an output is made to execute
the command.

Execute the SENS_ON command
only when an external encoder is
connected.

A.F10:
Main Circuit Cable

Open Phase
(With the main circuit

power supply ON, volt-

age was low for more

than 1 second in an R, S,

or T phase.)
(Detected when the main

power supply was turned

ON.)

The three-phase power supply

wiring is incorrect.

Check the power supply wiring.

Confirm that the power supply is

correctly wired.

The three-phase power supply is

unbalanced.

Measure the voltage at each phase

of the three-phase power supply.

Balance the power supply by chang-

ing phases.

The connection of the I/O signals

(CN901) between the SERVO-

PACK and converter is faulty.

Check the connection of CN901.

Correctly connect CN901.

A fault occurred in the SERVO-
PACK or converter.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK or con-
verter may be faulty. Replace the
SERVOPACK or converter.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions