background image

ConsoliDator Multi-Channel Controller

Instruction Manual

17

Analog Output Connections

The following figures show examples for 4-20 mA transmitter output connections. Terminal
connectors are labeled individually on the side of the case. In order to obtain isolation from
analog inputs, outputs must be powered from an external supply as shown in Figure 11.

Remote Display,

Chart Recorder, etc.

+

ANALOG OUTPUT

+24

LOOP IN

LOOP OUT

GND

Figure 10. 4-20 mA Output Powered by ConsoliDator

Remote Display,

Chart Recorder, etc.

+

ANALOG OUTPUTS

+24

External Power

Supply

+

LOOP

IN

LOOP

OUT

GND

Figure 11. 4-20 mA Output Powered by External Supply

Note: All inputs and outputs share a common ground. DO NOT power
inputs and outputs with the same power supply.