Input Scaling & Math Functions

The ConsoliDator is capable of various functions for scaling the 4-20 mA inputs. Linear
Square Root, Programmable Exponent, and Integration are two-point scaling functions.
Multi-Point is capable of handling up to 32 scaling points and requires that the ConsoliDator
Monitor Software be used to enter these points.




Linear

Linear mode refers to basic 2-point scaling of a 4-20 mA signal in engineering units.
The graph in Figure 17 shows the display response based on example scaling
parameters. For this mode select [Linear] from Function options, then follow Sensor
Input Setup
(page 29) to enter your scaling parameters.

Process Scaling

Parameters

Input

(mA)

Display

(%)

High Value:

100.00

Low Value:

0.00

4.00 0.00

Sensor:

20.00

Sensor:

4.00

5.00 6.25

Line a r Re sponse

0.00

20.00

40.00

60.00

80.00

100.00

4.00

8.00

12.00

16.00

20.00

Sensor (mA)

Display (%

)

6.00 12.50

7.00 18.75

8.00 25.00

9.00 31.25

10.00 37.50

11.00 43.75

12.00 50.00

13.00 56.25

14.00 62.50

15.00 68.75

16.00 75.00

17.00 81.25

18.00 87.50

19.00 93.75

20.00 100.00

Figure 17. Linear Response Graph