ConsoliDator Multi-Channel Controller

Instruction Manual

47

MODBUS

®

SERIAL COMMUNICATION

The controller is equipped with serial communication capability as a standard feature. Baud
Rate, Parity, Modbus ID (Address) and Transmit Delay are entered in the General
Functions
box, which appears in the main setup menu. The baud rate and parity selected
must match the settings for all other devices on the network. Modbus ID must be unique so
it will not interfere with other devices.

ConsoliDators support the following Modbus control functions:

Command

Name

Description

03

Read Holding Register

Read multiple bytes from holding registers.

05

Write Single Coil

Set single coil value control

06

Write Single Register

Set single value into specified holding register.

16

Write Multiple Registers

Set multiple values into specified holding registers.

Note: To save data to non-volatile memory after changing the contents of holding register(s) use the
Write Single Coil command [command code 05] to “ON” at address 64251.

To control the relays via MODBUS you would use the Write Single Coil command
[command code 05] and send either the “ON” or “OFF” to the appropriate alarm relay (1-9).

The ConsoliDator can also work as a "MODBUS Display" by setting the desired analog
input channel to the "FIXED" type and then over MODBUS change the "K-Factor/Modbus
Display" value for the corresponding channel. This input type is transparent to the rest of
the functions of the unit (i.e. relays, etc...). The value, once the EEPROM save command is
sent to the unit, is also maintained in EEPROM after the next power cycle.

Modbus Register Tables

Table 1. Analog Output Channels Register Addresses

Address (offset from 40000)

Description

Data Type

Ch. 1

Ch. 2

Ch. 3*

Ch. 4*

801

819

837 855

4 mA Value

Floating Point

802

820

838 856

803

821

839 857

20 mA Value

Floating Point

804

822

840 858

805

823

841 859

Set point Value

Floating Point

806

824

842 860

807

825

843 861

PID KP

Floating Point

808

826

844 862

809

827

845 863

PID KI

Floating Point

810

828

846 864

811

829

847 865

PID KD

Floating Point

812

830

848 866

813

831

849 867

PID Output Value

Floating Point

814

832

850 868

815

833

851 869

PID Cycle Time

Integer

816

834

852 870

Output Type

Byte

817

835

853 871

Input Ch.

Byte

818

836

854 872

PID Direction

Byte

*Channels 3-4 only apply to ConsoliDator 4 (PD940 & PD941) models.