background image

ConsoliDator Multi-Channel Controller

Instruction Manual

32

Multi-Channel High or Low
Alarm Modes

Multi-Channel High or Low modes
are used as an alarm triggered by a
set point common to the linked
channels.
Select [HIGH: Multi-Chan] from
Alarm Mode options to turn relay on
(energize) when high set point is
reached by any linked channel, and
off when all linked channels are
below reset point.
Select [Low: Multi-Chan] from Alarm
Mode
options to turn relay on
(energize) when low set point is
reached by any linked channel, and
off when all linked channels are
above reset point.

Alarm Setup: 1

Alarm Mode: HIGH: Multi-Chan

High Value: 160.0 GAL

Low Value: 8.0 GAL

Delay ON: 1.0 sec
Delay OFF: 0.5 sec

Link Channels:

1 2 3 4 5 6 7 8

EDIT

EXIT

ON:

Channel

Assign the relay to any analog or pulse input.

High Value

Enter high process variable set/reset point.

Low Value

Enter low process variable set/reset point.

Delay ON

Enter the delay between when the set point is reached and the
relay turns on (energizes.)

Delay OFF

Enter the delay between when the reset point is reached and the
relay turns off (de-energizes.)

Link Channels

Select the channels to link .