Multiple channel operation screen, Single analog input operation screen – Precision Digital PD941 User Manual

Page 42

Advertising
background image

ConsoliDator Multi-Channel Controller

Instruction Manual

42

Multiple Channel Operation
Screen

To the right is an example of a
multiple channel operation screen
for a four input application. The
screen reflects all of the inputs that
were detected or enabled during
setup. Depending on the actual
number of inputs in use, this screen
will adjust its size and proportions
automatically.

Note: It is recommended not to exceed 8
channels or graphics may overlap.

SETUP

AUTO

ACK

NEXT

Ch1

Ch2

Ch3

Ch4

Ch 1:

Ch 2:

Ch 3:

Ch 4:

13.000

14.000

15.000

mA

mA

mA

mA

mA

12.000

SETUP

Press to enter setup menu (Password restricted).

AUTO / MANUAL

The AUTO key indicates the unit is in Automatic mode. Press it to
switch to Manual mode. Press NEXT to return to main screen. Once
in Manual mode press MANUAL to switch to Automatic mode.
Note: The AUTO / MANUAL modes are password restricted.

ACK

Press to acknowledge (reset) the relays assigned to Supervisory,
Summary
or Annunciator Alarm functions and to silence the buzzer.

NEXT

Press to scroll to the next operation screen.

Single Analog Input
Operation Screen

For each analog input channel,
there is a detailed individual
channel operation screen, which
shows a bargraph with relay set
points, numerical values, sensor
input, and relay status for the relays
assigned to that particular channel.

100 ft

Ch 1:

87.5

ft

Sensor In: 18.00 mA

Rly: Low: High:

2: 40.0 50.0 ON
3: 8.0 20.0 ON

H2
L2

H3

L3

0 ft

SETUP

AUTO

ACK

NEXT

SIM

SETUP

Press to enter setup menu (Password restricted).

AUTO / MANUAL

The AUTO key indicates the unit is in Automatic mode. Press it to
switch to Manual mode. Press NEXT to return to main screen. Once
in Manual mode press MANUAL to switch to Automatic mode.
Note: The AUTO / MANUAL modes are password restricted.

SIM / RST

Press to enter a simulation mode where the input can be adjusted
manually. (Password restricted.) If the channel is set for Integration
totalizing, the SIM key is replaced by RST, which is used to reset
the total to zero (Password restricted.)

ACK

Press to acknowledge (reset) the relays assigned to Supervisory,
Summary
or Annunciator Alarm functions and to silence the buzzer.

NEXT

Press to scroll to the next operation screen.

Advertising