Solare Datensysteme Solar-Log User Manual

Page 141

Advertising
background image

141

Special functions

23�3�3 Fixed reactive power in Var

Reactive Power Management

This function allows the connected inverters to generate a certain reactive power in Var for a definable

period of time.

Procedure:

Select Fixed reactive power in

Var

.

Activate the interfaces.

Enter the

from (time)

.

Enter the

Reactive power

for this time period.

Check the box

Inductive/under-excited

for reactive power.

If necessary, enter additional times and the accompanying reactive power

SAVE

settings.

If a certain reactive power in

Var

must be supplied for 24 hours, the time 00:00 as well as the value in Var

have to be entered in the first line along with checking the Inductive box. The other lines must also be filled

with 00:00. It is not necessary to enter reactive power.

Reductions

The following configuration options are available in the Reductions section.

Max. cos(phi) inductive/underexcited and max. cos(phi) capacitive/over-excited:
A maximum shift factor can be defined wit this the reduction. With this, it can be that less reactive
power is fed-in into the grid than allowed in the partial load range in order to maintain the shift
factor limits.

Note

Entering zero as the value deactivates the particular limit.