Configuring connected devices

Input definition section

The following CTs are available:
Solar-Log™ CT 16A
Solar-Log™ CT 100A - C
Solar-Log™ CT 100A - o
user-defined

The settings for the Solar-Log™ CTs have been pre-defined for the current ratio.

When using other CTs, select user-defined.
An additional input box appears for the current ratio of the installed CT.
The current ratio is calculated with the ratio between primary and secondary current

Example

200A of primary current results into 200mA of secondary current with a user-defined current trans-
former.
There is then a the current ratio of 100 (200A/0.2A) Enter this value (1000)

in the field

Current Ratio.

Reference voltage section

In addition to the current measured by the CT, a reference voltage is needed for the power output calcula-

tion. This reference voltage can either be

recorded via the inverters and/or calculated by the Solar-Log™

or set in the box reference voltage [V].

If the Solar-Log™ does not receive voltage values from the inverters (for example during night), an average

value is calculated and used.

By activating the

Always use stored voltage button

, the value entered in the reference voltage [V] input

box is always used for the power output calculation.

Note

The reference voltage value is predefined by the country settings. Please check this

value.

It is best to measure the reference voltage and enter this value.

During the

Device Detection

process, the CT defined here is

recognized as a meter

and can be adjusted

and named accordingly in the meter configuration menu under

Configuration | Devices | Configuration

.