183

Direct Device Configurations (Solar-Log 1000)

Enter the number of the module field and confirm with OK.

Touch Save and then Next to go to the next dialog.

Dialog for multi-string inverters

String

Display field only, not editable: Module string numbers

Module field

Module field numbers can be used to assign the same types of strings or inverters. In the plant monitoring,

only strings or inverters with the same module field number are offset against each other.

Connected module power

For inverters or strings (in multi-string inverters only), the connected module power must be indicated in

the exact total module power.

Example: 28  160 Watt modules = 4480

Name

The name of the string that is shown on the homepage or yield overview (for multi-string inverters only).

How to enter the module and power data:

Touch the input box for the module field.
The virtual keyboard appears.

Enter the number of the module field and confirm with OK.

Touch the input box for the module field.
The virtual keyboard appears.

Enter the desired module power and confirm with OK.

Touch the input box for the name.
The virtual keyboard appears.

Enter the name of the string and confirm with OK.

Touch Save and then Next to go to the next dialog.

Configuring graphic scaling

Only the Y-axis representation (power output displayed) can be configured from the display for the

graphic display of yield data.

Nothing usually has to be changed here, as Solar-Log 1000 automatically calculates the values for the gen-

erator power input. However, these values can be adapted to your own data.

To set the representation on the y-axis:

Touch the required input box beside Day, Month, Year and/or All Years.
The virtual keyboard appears.

Enter the maximum value to be represented on the Y-axis and confirm with OK.

Touch Save