MVI46-MCM ♦ SLC Platform

Configuring the MVI46-MCM Module

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 19 of 108

March 29, 2011

File M0

Offset

Register

Content

Description

N10:16

17

5016

Baud Rate

This is the baud rate to be used on the port. Enter
the baud rate as a value. For example, to select
19K baud, enter 19200. Exceptions: 38400 baud,
enter 384. 57600 enter 576. 115000 enter 115.

N10:17

18

5017

Parity

This is the parity code to be used on the port. The
coded values are as follows:
0=None
1=Odd
2=Even

N10:18

19

5018

Data Bits

This parameter sets the number of data bits for
each word used by the protocol. Enter a value in
the range of 5 to 8.

N10:19

20

5019

Stop Bits

This parameter sets the number of stop bits for
each data value sent. Enter a value of 1 or 2.

N10:20

21

5020

RTS On Delay

This parameter sets the number of milliseconds to
delay after RTS is asserted before the data will be
transmitted. Enter a value in the range of 0 to
65535.

N10:21

22

5021

RTS Off Delay

This parameter sets the number of milliseconds to
delay after the last byte of data is sent before the
RTS modem signal will be set low. Enter a value in
the range of 0 to 65535.

N10:22 23

5022

Minimum

Response

Delay

This parameter sets the number of milliseconds to
wait before a response message is sent out of the
port. This parameter is required when interfacing to
a slow responding device. Enter a value in the
range of 0 to 65535.

N10:23

24

5023

Use CTS Line

This parameter specifies if the CTS modem control
line is to be used. If the parameter is set to 0, the
CTS line will not be monitored. If the parameter is
set to 1, the CTS line will be monitored and must be
high before the module will send data. Normally,
this parameter is required when half-duplex
modems are used for communication (2-wire).

N10:24

25

5024

Slave ID

This parameter defines the virtual Modbus slave
address for the internal database. Any requests
received by the port with this address will be
processed by the module. Verify that each device
has a unique address on the network.

N10:25

26

5025

Bit Input Offset

This parameter specifies the offset address in the
internal Modbus database for network requests for
Modbus function 2 commands. For example, if the
value is set to 150, an address request of 0 will
return the value at register 150 in the database.

N10:26

27

5026

Word Input Offset

This parameter specifies the offset address in the
internal Modbus database for network requests for
Modbus function 4 commands. For example, if the
value is set to 150, an address request of 0 will
return the value at register 150 in the database.