ProSoft Technology MVI46-MCM User Manual

Page 41

Advertising
background image

MVI46-MCM ♦ SLC Platform

Diagnostics and Troubleshooting

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 41 of 108

March 29, 2011

Viewing the Slave Status List (Port 1 and 2)

Press [O] (port 1) or [P] (port 2) to view the 256 slave status values associated
with the ports.
 0 = slave is not used
 1 = slave being actively polled
 2 = slave suspended
 3 = slave disabled.

Viewing Version Information

Press [V]

to view version information for the module.

Use this command to view the current version of the software for the module, as
well as other important values. You may be asked to provide this information
when calling for technical support on the product.

Values at the bottom of the display are important in determining module
operation. The Program Scan Counter value is incremented each time a
module’s program cycle is complete.

Tip: Repeat this command at one-second intervals to determine the frequency of program
execution.

Warm Booting the Module

Press [W]

from the Main menu to warm boot (restart) the module.

This command will cause the program to exit and reload, refreshing configuration
parameters that must be set on program initialization. Only use this command if
you must force the module to reboot.

Advertising