ProSoft Technology MVI46-MCM User Manual

Page 65

Advertising
background image

MVI46-MCM ♦ SLC Platform

Reference

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 65 of 108

March 29, 2011

Event Command Blocks (1000 or 2000)

Event command control blocks send Modbus Master/Slave commands directly
from the ladder logic to one of the master ports.

Block Request from Processor to Module

M1 Offset

Description

Length

7800

1000 or 2000

1

7801

Internal DB Address

1

7802 Point

Count

1

7803 Swap

Code

1

7804 Node

Address

1

7805 Function

Code

1

7806 Device

Address

1

The block number defines the Modbus Master/Slave port to be considered. Block
1000 commands are directed to Port 1, and block 2000 commands are directed
to Port 2. Use the parameters passed with the block to construct the command.
The Internal DB Address parameter specifies the module’s database location to
associate with the command. The Point Count parameter defines the number of
registers for the command. The Swap Code changes the word or byte order. The
Node Address parameter defines the device on the Modbus Master/Slave
network to consider. The Function Code parameter is one of those defined in
the ProSoft Modbus Master/Slave Command Set documentation. When the block
is received, the module will process it and place the command in the command
queue.

Block Response from Module to Processor

M0 Offset

Description

Length

0

1000 or 2000

1

1 0=Fail,

1=Success

1

The ladder logic can use Word one of the block to determine if the command was
added to the command queue of the module. The command will only fail if the
command queue for the port is full (100 commands for each queue) or the
command requested is invalid.